Heat Pumps
Improving
Performance
Poor installation,
duct losses, and inadequate maintenance are more of a problem for heat
pumps than for combustion furnaces. A growing body of evidence suggests
that most heat pumps have significant installation or service problems
that reduce performance and efficiency.
According to a report on research funded by Energy Star‚ more than 50
percent of all heat pumps have significant problems with low airflow,
leaky ducts, and incorrect refrigerant charge.
Increasing
airflow in central heat pumps
The capacity and the
efficiency of a heat pump depend upon adequate airflow. There should be
about 400 to 500 cubic feet per minute (cfm) airflow for each ton of the
heat pump's air-conditioning capacity. Efficiency and performance
deteriorate if airflow is much less than 350 cfm per ton.
An ideal duct system has both a supply register and a return register
for every room. Most homes, however, have only one or two return
registers for the entire house. Air from other rooms must find its way
back to these registers to be reheated or re-cooled. Obstructions in
return air are a common air circulation problem, particularly from
closed interior doors to rooms with no return-air register.
Blockage of supply or return air ducts and registers can pressurize or
depressurize portions of the home, resulting in poor performance and
increased air leakage through the building envelope. Restrictions to
airflow have the greatest impact on the return-air side of the system,
so repairs should start with the return ducts.
Air from every supply register must have an unobstructed pathway back to
a return register. You can install louvered grilles through walls or
doors, ducts between rooms, and/or additional return ducts and registers
to improve air circulation.
Technicians can increase the airflow by cleaning the evaporator coil,
increasing fan speed, or enlarging the ducts—especially return ducts.
Enlarging ducts may seem drastic but in some cases, might be the only
remedy for poor comfort and high energy costs.
Air-sealing ducts
Measurements of heat
pump performance indicate that duct leakage wastes 10 to 30 percent of
the heating and/or cooling energy in a typical home. It's one of the
most severe energy problems commonly found in homes because the leaking
air is 20° to 70°F warmer than indoor air in winter and 15° to 30°F
cooler in the summer.
Duct leakage may cause some minor comfort problems when ducts are
located in conditioned areas. But when leaky ducts are located in an
attic or crawl space, the energy loss is often large. Some of the worst
duct leakage occurs at joints between the air handler, and the main
supply and return air ducts. Some main return ducts use plywood or
fiberglass duct-board boxes. These boxes frequently leak because their
joints are exposed to the duct system's highest air pressures. Heating
and air-conditioning contractors often use wall, floor, and ceiling
cavities as return ducts. These building-cavity return ducts are often
accidentally connected to an attic, crawl space, or even the outdoors,
creating serious air leakage. Fiberglass ducts and flex ducts are often
installed improperly. These ducts may also deteriorate with age, leading
to significant supply-duct leakage.
The best heating and cooling contractors have equipment to test for duct
leakage. Testing helps locate duct leaks and indicates how much duct
sealing is necessary. Do not use duct tape for sealing—its life span is
very short, often less than 6 months.
Adjusting
refrigerant charge
Room heat pumps and
packaged heat pumps are charged with refrigerant at the factory. They
are seldom incorrectly charged. Split-system heat pumps, on the other
hand, are charged in the field, which can sometimes result in either too
much or too little refrigerant.
Split-system heat pumps that have the correct refrigerant charge and
airflow usually perform very close to manufacturer's listed SEER and
HSPF. Too much or too little refrigerant, however, reduces heat-pump
performance and efficiency.
For satisfactory performance and efficiency, a split-system heat pump
should be within a few ounces of the correct charge, specified by the
manufacturer. When the charge is correct, specific refrigerant
temperatures and pressures listed by the manufacturer will match
temperatures and pressures measured by your service technician. Verify
these measurements with the technician. If the manufacturer's
temperatures and pressure's don't match the measured ones, refrigerant
should be added or withdrawn, according to standards specified by the
EPA.
Refrigeration systems should be leak-checked at installation and during
each service call. Manufacturer's say that a technician must measure
airflow prior to checking refrigerant charge because the refrigerant
measurements aren't accurate unless airflow is correct.
http://www.eren.doe.gov/erec/factsheets/airheatpump.html
|
|